Halstock stainless steel calorifier
Stainless steel single coil and twin coil calorifiers for indirect hot water.
5 unvented calorifier models and 4 open-vented calorifiers available with continuous outputs (@44°C ∆T) of 390, 527, 1,843 and 2,106 l/h.
Product information
- Power outputs 20-108kW and storage capacities 305-965 litres
- Indirect method of producing safe and hygienic domestic hot water (want to understand the difference between Indirect vs Direct Hot Water Systems?)
- Fast recovery for constant hot water – as little as 13 minutes (Recovery times for 70% of the cylinder volume to 50°C 13-22 minutes)
- Hot water cylinder and coil made out of corrosion resistant stainless steel for a long life backed up by a 5 year cylinder warranty
- Now available with twin coils for flexibility and high performance hot water (models 500-965 only)
- Can be integrated with solar thermal for a renewable energy option
- Minimal heat loss for maximum economy thanks to layer of CFC-free polyurethane tank insulation under protective plastisol cladding
- Highly efficient heat transfer from a corrugated coil design
- Low maintenance as no sacrificial anodes or powered corrosion protection systems needed
- Can be located wherever convenient
- Versatility in use – coupled to Hamworthy commercial boilers or backup via immersion heater
- UK manufactured hot water calorifiers
- Compliant with Energy Labelling requirements of ErP
- Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).
Technical data
Units | HS305 | |
---|---|---|
Water | ||
Capacity, nominal | litres | 305 |
Capacity with coil | litres | 298 |
Continuous output @44°C ΔT | l/h | 390 |
Continuous output @50°C ΔT | l/h | 344 |
Maximum working pressure, tank | bar | 6 |
Hydraulic test pressure | bar | 9 |
Energy | ||
Number of coils | 1 | |
Lower coil output | kW | 20 |
Heat up time @50°C ΔT,lower coil only | min | 54 |
Upper coil output | kW | N/A |
Heat up time @50°C ΔT,top coil only | min | N/A |
Heat up time @50°C ΔT,combined coils | min | N/A |
Recovery time 70% @50°C ΔT, combined coils | min | 38 |
10 min peak output @50°C ΔT | litres | 361 |
Coil max operating temperature | °C | 100 |
Coil max operating pressure | bar | 3 |
Upper coil tube diameter | DN | NA |
Upper coil surface area | m2 | NA |
Lower coil tube diameter | DN | DN20 |
Lower coil surface area | m2 | 0.75 |
Reheat total delta T 50degC lower | mins | 38 |
Reheat total delta T 50degC both | mins | N/A |
Standby losses | kW/24hr | 1.77 |
ErP efficiency rating | - | C |
Immersion | ||
Immersion heater option, power | kW | 3 |
Immersion heater option, phase | ph | 1ph |
Heat up time, Immersion only | hour | 5.8 |
Recovery time, Immersion only | hour | 4.1 |
Misc. | ||
Expansion vessel size | litres | 24 |
Weight empty | kg | 75 |
Weight full | kg | 379 |
Ideal uses/applications
- To provide domestic hot water for any type of commercial building.
- Designed for use with natural gas, LPG or oil-fired commercial boilers for primary heat source.
- Direct heating via optional Incoloy 800 electrical immersion heaters.
- Suited to all areas of the UK, particularly locations with soft water (read here why).
Optional extras
- Electric immersion heater kits
- Top-to-bottom re-circulation/de-stratification kit to prevent stratification and protect against legionella within the water heater (factory fitted – please specify at time of ordering)
- Choose from a wide range of service contracts to help maintain optimum performance.