Upton floor standing modular boiler
Space saving, fully modulating condensing pre-mix floor standing boiler with aluminium heat exchanger.
Available in 6 modules with outputs (@50/30°C) of 98, 147, 197, 246, 295 and 348kW. Individual boiler modules can be stacked one, two or three high in up to 18 combinations, maximum 1,046kW.
Product information
- Small footprint – get over 1MW from less than 1 metre squared footprint
- Aluminium heat exchanger provides excellent heat transfer properties and a 5-year warranty
- Quick to respond with low water content
- Lightweight and compact modular boiler – ideal for city centre developments
- Parallel water flow for an even surface temperature across the aluminium heat exchanger
- Highly efficient up to 97% gross seasonal efficiency exceeds legislation and reduces energy use
- High turndown ratio for close load matching further improves efficiencies
- Assists designers with changing project requirements - gas and water connection positions identical on all models
- Easy access for service and system cleaning – combustion analysis and drain point at front of boiler
- Built in boiler sequence controls capable of controlling up to 16 boiler modules and hot water circuits
- Low noise to enable installation close to building occupants
- Environmentally friendly low NOx emission (European Class 6)
- 6 bar rated heat cell
- Air inlet filter for clean combustion and reduced noise
- Simplified primary circuit design with a choice of complete optional kits from Hamworthy to include – flow and return pipework kit, optional matched boiler pumps, low loss header with combined air and dirt separator, connection points and manifold extension kits (Please note: We are currently changing our pipework kits. To confirm which pipe kit you need to specify please talk to your local contact)
- BIM objects available to assist in design and management
- MCPD - The Medium Combustion Plant Directive (MCPD) is legislation that regulates individual combustion plants with a rated thermal input greater than or equal to 1MW but less than 50MW. The Upton UF1050-3 falls into this category. The boiler is compliant with the emission limit values but registration/permission is required from the relevant authority before the plant can be put to service. Find out more here.
Technical data
Units | UF100-1 | |
---|---|---|
No. of modules | 1 | |
Energy | ||
Building Regulations Part L seasonal efficiency | % gross | 97.4 |
Building Regulations Part L seasonal efficiency | % nett | 108.2 |
Boiler output 80/60°C | kW | 89.1 |
Boiler output 50/30°C | kW | 98.6 |
Boiler input gross (maximum) | kW | 103 |
Boiler input nett (maximum) | kW | 92.8 |
Boiler output 80/60°C (minimum) | kW | 17.8 |
Boiler output 50/30°C (minimum) | kW | 19.7 |
Water | ||
Water content | litres | 9 |
System design flow rate @ 11°C ∆T rise | l/s | 2.2 |
Water side pressure loss @ 11°C ∆T rise | mbar | 736 |
System design flow rate @ 20°C ∆T rise | l/s | 1.2 |
Water side pressure loss @ 20°C ∆T rise | mbar | 225 |
Minimum operating water pressure | barg | 0.5 |
Maximum operating water pressure | barg | 5.3 |
Maximum water pressure | barg | 6 |
Maximum flow temperature setting | °C | 85 |
Minimum flow temperature setting | °C | 30 |
Gas | ||
Gas flow rate (maximum) (Nat gas) | m3/hr | 9.8 |
Gas flow rate (maximum) (LPG) | m3/hr | 3.8 |
Nominal inlet pressure (Nat gas) | mbar | 20 |
Nominal inlet pressure (LPG) | mbar | 37 |
Maximum inlet pressure (Nat gas) | mbar | 25 |
Maximum inlet pressure (LPG) | mbar | 45 |
Flue | ||
Approx flue gas volume @ 72°C , 9.0% CO2 | m3/hr | 155 |
Maximum flue gas temperature @ 80/60°C | °C | 72 |
Maximum flue gas temperature @ 50/30°C | °C | 42 |
Pressure available at flue connection | Pa mbar | 150 1.5 |
NOx Class | 6 | |
Connection | ||
Water flow/return connections | inches | R2-11 |
Gas inlet connection pipe thread size | inches | G1¼ |
Flue connection diameter (I/D) | mm | 130 |
Condensate trap connections (O/D) | mm | 34 |
Electrics | ||
Electrical supply | 230V ~ 50Hz | |
Power consumption - maximum boiler modulation | W | 139 |
Run current (per module) | Amp | 0.6 |
Others | ||
Approx shipping weight | kg | 152 |
Noise emission @1m @max modulation (per module) | Max dB (A) | 55.8 |
Downloads
Upton boiler brochureProduct brochures 9565 kb |
Download | |
500001305-B QAA73.210 Programmable Room Unit Guide.pdfInstallers guides 1783 kb |
Download | |
AGU 2.550 Kit instructionsInstallers guides 445 kb |
Download | |
LPB Expansion Kit InstructionsInstallers guides 2358 kb |
Download | |
Navistem B3000 controller instruction manualInstallers guides 2177 kb |
Download | |
QAA55 room unit programming instructionsInstallers guides 153 kb |
Download | |
QAA74 - Technical ManualInstallers guides 1640 kb |
Download | |
QAA74 Quick Reference GuideInstallers guides 178 kb |
Download | |
Siemens room operator units QAA55, QAA75, QAA78, AVS13, AVS14, AVS71Installers guides 6621 kb |
Download | |
Upton boiler installation, commissioning and operating manualInstallers guides 9664 kb |
Download | |
Upton boiler pipe kit manual.pdfInstallers guides 5579 kb |
Download |
Ideal uses/applications
- New build projects
- City centre, roof top and basement plantrooms
- Restricted space plantrooms
- Large commercial and public buildings including schools, hospitals and hotels
- Medium sized commercial and public buildings including schools, hospitals, offices and hotels
- Locations with substantial and continuous heating load including hospitals, care homes and hotels
Optional extras
- Pipework header kits to include matched boiler pumps, safety relief valve and automatic air vent (Please note: We are currently changing our pipework kits. To confirm which pipe kit you need to specify please talk to your local contact)
- Low loss header with integrated air and dirt separator (Want to know 'What is a low loss header?')
- 3 port extension manifold
- Blanking plates with tappings for system safety relief valve and pressurisation unit
- Multiple boiler controls
- Room & outside temperature sensors
- LPB bus communications modules
- Zone control
- DHW cylinder sensor kit
- Flues available
- Single Boiler Controls
- Multiple Boiler Controls
- Choose from a wide range of service contracts to help maintain optimum performance
- Book commissioning at the same time as placing your order for improved warranty terms.